DSEAR risk assessment at a seed blending site

An agricultural seed blending business in southern Scotland asked IDEA for its first DSEAR risk assessment. We assessed three areas and six fire and explosion scenarios, treated the grass seed dust as explosive in the absence of test data, and issued 13 prioritised actions. The most serious risk sat outside the equipment, in dust settled on surfaces in the building, so housekeeping became the main control.

At a glance

  • Sector: Agriculture (seed processing)
  • Scope: First DSEAR risk assessment for the site
  • Disciplines: Process Safety
  • Outcome: 3 areas and 6 scenarios assessed; 13 actions, ranked by risk

Client Overview

The client blends seed varieties to customer order, bags the blends and despatches them on pallets. The site runs three blending lines, a dust extraction unit and a diesel tank for forklift fuelling, all within one building. It had never had a DSEAR risk assessment.

The challenge: a first assessment for a dust-handling site

Seed handling creates organic dust at every transfer point: bag emptying, screw conveyors, cleaning, bucket elevators, mixing silos and bag filling. Under the Dangerous Substances and Explosive Atmospheres Regulations 2002 (DSEAR), a dust that can form an explosive cloud in air is a dangerous substance, and the employer must assess the risk before work is carried out.

The client needed an assessment proportionate to a small operation. No explosibility test data existed for its seed dusts, so the first question was what basis to assess on.

IDEA's role

IDEA carried out the DSEAR risk assessment for the whole site. Scope was the risk assessment under regulation 5; hazardous area classification under regulation 7 was outside this project. A senior process safety engineer surveyed the site with the client's team, watched the lines in operation, and prepared the worksheets and report. Our process safety director checked and approved the report before issue.

What we delivered

A clear basis for the dust. With no test data, we assumed the grass seed dust is explosive. This is the cautious position, and it is consistent with HSE guidance that grain, flour and similar dusts can form explosive atmospheres. We also recommended testing: if the dust proves not to be explosive, the dust scenarios fall away.

Scenario-by-scenario risk assessment. Each scenario was ranked on IDEA's risk matrix before and after the recommended actions, with ignition sources reviewed against the categories in BS EN 1127-1 (hot surfaces, flames, mechanical sparks, electrical equipment and static).

Scenario Risk now After actions
Explosion in the dust collection unit Tolerable if ALARP Broadly acceptable
Explosion at a bag filling station Broadly acceptable Broadly acceptable (no action needed)
Explosion in conveying equipment Broadly acceptable Broadly acceptable, with lower likelihood
Explosion in a mixing silo Broadly acceptable Broadly acceptable, with lower likelihood
Secondary dust explosion in the building Tolerable if ALARP Tolerable if ALARP; housekeeping is the key control
Diesel pool fire at the storage tank No DSEAR risk identified No DSEAR risk identified

ALARP: as low as reasonably practicable. 

Thirteen actions, ranked by risk. They fall into four groups:

  • Housekeeping: empty the dust collection unit on a routine schedule rather than when suction drops at the filling stations; stop dust building up around the unit, the lines and especially the motors; use an ATEX-rated vacuum cleaner for clean-up.
  • Explosion isolation and maintenance: fit an explosion-proof non-return valve in the extraction ducting so an explosion in the collector cannot travel back into the process; service the unit and its explosion relief panel to the manufacturer's recommendations.
  • Ignition control: anti-static conveying equipment, earthed silos, and choke detection on conveyors to catch overheating bearings and motors.
  • Next steps: dust explosibility testing, hazardous area classification to confirm any ATEX equipment requirements, DSEAR training for staff, and a local spill kit at the diesel tank.

Training requirements by role, from senior management (legal duties) to maintenance staff (equipment in hazardous areas), in line with the information and training duty in regulation 9.

Results and outcome

The client now has a documented DSEAR risk assessment where none existed, a stated basis of safety for each scenario, and a short list of actions it can complete in order of risk.

The assessment also showed where the risk really sits. The highest-consequence scenario sat in the building itself: dust settled on motors and ducting can be raised by a small primary event into a much larger secondary explosion. Several of the controls that matter most are therefore routine procedures that need little capital spend.

The diesel tank was assessed and found to present no credible DSEAR risk, because the fuel is handled at ambient temperature well below its flash point. A proportionate assessment records that conclusion rather than adding controls that do nothing.

Why IDEA for process liquid handling design

We assess combustible dust in the equipment where it is generated: intake, conveying, elevators, mixers, filling and extraction. The same unit operations appear in malt intake and milling at distilleries and breweries, where much of our DSEAR work has been delivered, and our assessments are checked and approved by a process safety director before issue. Find out more about our DSEAR risk assessment and hazardous area classification services.

Read more

Frequently Asked Questions

Yes, if they can form an explosive cloud when dispersed in air. HSE lists grain and flour among dusts that can explode. Whether a particular seed dust is explosive depends on factors such as particle size and moisture, so testing gives a definite answer. Until then, assessing it as explosive is the cautious basis.

No. The risk assessment (regulation 5) identifies fire and explosion risks from dangerous substances and the measures to control them. Hazardous area classification (regulation 7) divides places where explosive atmospheres may occur into zones, which sets the standard of equipment allowed there. A first assessment often recommends classification as the next step, as it did here.

Dust settled on equipment and surfaces can be raised into a cloud by a small fire or explosion. The resulting secondary explosion can be larger and more damaging than the first event. Keeping dust layers to a minimum is therefore one of the most effective controls on these sites.

It should be assessed. On this site the diesel is stored in a bunded tank and handled at ambient temperature, well below its flash point, so a pool fire was not considered credible and no DSEAR risk was identified. A spill kit was still recommended as good practice.